SYSTEM INSTALL CHECKLIST MUST BE COMPLETED BEFORE COMPLETING INSTALL Customer Name Technician Wash hands prior to installing thermostats, wall and ceiling grilles, and registersAll penetrations sleevedAll penetrations siliconed or mortaredOn 15KW heat packs amp draw 38 to 48 on 6/2 wire and 19 to 20 amps on 10/2 WireLevel padSoap test all gas lines we touchedFlue pipe strapped every 4 feetCheck flue pipe with level for 1/8" per floot slopeIs the ductwork 100% sealed from the Aprilaire cabinet to the equipment cabinet?Did the humidifier operate from the thermostat or humidistat?All wires strapped down?Are all wires not crossing or wrapped around pipes or each other?Did you add onto wires and not stretch them to reach?Does s-lock reach the corners of the metal?Is the plenum and new transitions sealed from the inside?The final piece of metal is the only one that can be sealed from the outsideFlex should be pulled with a loose fit. Not too tight and not too looseFlex insulation should cover take offs completely with no metal showingOne zip tie on inner lining with 3 metal rings pulled to metal then one zip tie around insulation pulled all the way to metalRuns should not cross each other unless necessaryAll ductwork must be wrapped in unconditioned spacesAll boxes and the trunk must be wrapped before take offs are installedAll holes must be cut into metal prior to wrapping ductworkAll PVC fittings must have cleaner or primer used prior to glueAre all pipes straight and strapped in place?Is the system stacked straight and screwed down?Slick down silicone!Seal all gaps around ductwork and plenum in the ceiling with metal or siliconeThum gum linesets (exterior and at coil) and holes in coilDid the humidifier operate from the thermostat or humidistat?Did all equipment tests run the full 5 minutes without short cycling?TEMPERATURE CHECKSSupply degrees after ran 5 minutes: Supply degrees after heat pump only ran 5 minutes: Supply degrees after AUX heat ran 5 Minutes: Supply degrees after cooling ran 5 minutes: Return degrees: Degrees in house at checkout time: OUTDOOR HEAT PUMP CDA UNDER CONFIGURE MENUIf power company has a box on the house, set inactive switch to onMinimum airflow speed - Set to 50 for non-zoned systemsMinimum airflow speed - Set to 50 for zoned systemsMinimum capacity - Set to 50 for zoned systemsMinimum capacity - Leave on factory for zoned systemsDefrost Control - Set from factory to HighIndoor air cooling - Set to ComfortIndoor air heating - Set to EfficiencyAIR HANDLER CDA UNDER CONFIGURE MENUSet air handler for proper KW of backup heatSet airflow for heating to 430 per tonSet airflow for cooling to 400 per tonOther mentionsImportant notes regarding this install: